Heating, Cooling & HVAC

Steam condensate recovery system (LPMP pumps)

Part no.
BD-1239
Brand
Argonmark
Available on order · sourced to your specification
Price on request

Pricing depends on specification, quantity and delivery location. Send your requirement and we reply with a costed quotation within 24 hours.

Quick overview

  • Type: Boiler & Steam
  • Models: HPT10, HP10, HPT30, HP30
  • Configuration: Single or double pump system (pumps in parallel)
  • Motive medium: Steam or compressed air
  • Pump inlet / outlet: DN80 × DN50
  • Connection: RF DIN PN16 (DN80); Sc 1/2" (DN15)
Call +880 1713 552466
  • Genuine productsSourced from the manufacturer or authorised channels
  • Delivery across BangladeshDhaka, Chattogram and all industrial zones
  • After-sales supportInstallation guidance and warranty handling
  • Reply within 24 hoursCall +880 1713 552466 or email hello@argonmark.com

Specifications

General
Part no.BD-1239
CategoryBoilers, Steam & Heat Transfer
GroupHeating, Cooling & HVAC
BrandArgonmark
Technical
TypeBoiler & Steam
ModelsHPT10, HP10, HPT30, HP30
ConfigurationSingle or double pump system (pumps in parallel)
Motive mediumSteam or compressed air
Pump inlet / outletDN80 × DN50
ConnectionRF DIN PN16 (DN80); Sc 1/2" (DN15)
Pressure ratingTest pressure 13.8 MPa
Working temperature≤ 180°C

Datasheet

Design standard

Design & manufactureJB/T 11170-2011
Discharges 25 kg of condensate at each working cycle
Weld seam thickness more than 6 mm at each welding position

Technical features

Self-contained pumps driven by steam or other pressurised gas; recover condensate (or other fluids) under all operating conditions
Suitable for hazardous areas where electrical pumps are not, and for efficient drainage of heat exchangers
Recovering condensate improves production efficiency, reduces water-treatment cost and uses steam fully
Eliminates water hammer, avoiding equipment damage and improving reliability and safety
Reduces boiler fuel cost and down-stream water treatment and drainage
Recovers condensate up to 185°C without evaporation
Selectioncheck max. flow rate, the motive medium's pressure and temperature, and total back pressure (vertical lift, condensate line pressure, pipe/valve/fitting losses)
Motive pressure supplied by the customer must be 0.1–0.15 MPa higher than the total back pressure

Main performance specification

Test pressure13.8 MPa
Shell test4.0 MPa, 10 min
Seal test0.6 MPa, 5 min
Working testMore than 200 times
Suitable temperature≤ 180°C
Unit body seal0.6 MPa, 10 min
Tank test (closed system)2.5 MPa, 5 min

Main parts materials

No.PartMaterial
1Set water tankAssembly
2Inlet assemblyAssembly
3Pump bodyWCB
4TrimSS
5Outlet assemblyAssembly
6Driving air pipeAssembly
7Air vent pipeAssembly
8GasketGraphite + SS
9Drain plug45#
10Studs8.8

Quantity 1 of each part.

Main dimensions (mm)

TypeLWH
Single pump system assembly11507501670
Double pump system assembly117011501760

Pump body dimensions (mm)

TypeABCD
Pump body340540540130

Connections

CodeNameSizeConnection
aInletDN80RF DIN PN16
bAir ventDN80RF DIN PN16
cOverflowDN80RF DIN PN16
dDriving airDN15Sc 1/2"
eDrainDN15Sc 1/2"

Selection: back pressure / driving pressure factor

Back / driving pressure10%20%30%40%50%60%70%80%90%
Pump inlet size factor1.041.061.081.101.121.151.181.231.28

Capacity, pump DN80 × DN50

Driving pressureBack pressureSingle pumpDouble pump
21.040508100
41.0602012040
42.041008200
43.021604320
51.0673013460
52.047709540
53.033306660
54.019003800
72.0558011160
73.044106620
74.037807560
75.031506300
9.53.0648012960
9.54.0567011340
9.55.046809360
9.56.036907380
9.57.030603120
124.0639012780
125.0558011160
126.044108820
127.037607560
128.031506300
13.85.0612012240
13.86.049509900
13.87.042305460
13.88.036907360
13.89.034206640

Values as printed on the supplier's select datasheet. Units are not stated in the table; the order form uses bar for pressures and kg/h for condensate.

Notes

Order requirementsdriving medium (compressed air or saturated steam), driving pressure (bar), back pressure (bar), condensate (kg/h).

Description

Steam condensate recovery system. Collects hot condensate and pumps it back to the boiler. Saves water, fuel and treatment chemicals.

Argonmark Ltd supplies this item to factories, power plants, utilities, contractors and government projects across Bangladesh. Send us the required size, rating, materials and quantity and we will reply with a quotation within 24 hours.

Questions & answers

Customer questions

No questions asked yet. Ask about specification, compatibility, lead time or anything else about this item.

Ask a question

Please don’t include links. Questions are published together with our answer.

Reviews

No reviews yet. Bought or used this item? Be the first to share your experience.

Write a review

Your rating

Reviews are checked before they appear.

Price on requestQuote within 24 hours

Request a quotation

Steam condensate recovery system (LPMP pumps)
Part no. BD-1239

Opens your email app with this request filled in. We reply within 24 hours.