Endress+Hauser Proline Promag P 300 electromagnetic flow meter, DN 15–600, PTFE/PFA liner to 180 °C, compact, up to 3 I/Os, Ex
Pricing depends on specification, quantity and delivery location. Send your requirement and we reply with a costed quotation within 24 hours.
Quick overview
- Type: Electromagnetic flow meter
- Signal / Protocol: 4–20 mA, HART, Modbus, PROFIBUS, RS-485, Pulse / frequency
- Hazardous area: Hazardous-area rated / option
- Genuine productsSourced from the manufacturer or authorised channels
- Delivery across BangladeshDhaka, Chattogram and all industrial zones
- After-sales supportInstallation guidance and warranty handling
- Reply within 24 hoursCall +880 1713 552466 or email hello@argonmark.com
Specifications
| General | |
|---|---|
| Part no. | BD-1611 |
| Category | Flow Meters |
| Group | Instrumentation & Control |
| Brand | Endress+Hauser |
| Model | Proline Promag P 300 |
| Technical | |
| Type | Electromagnetic flow meter |
| Signal / Protocol | 4–20 mA, HART, Modbus, PROFIBUS, RS-485, Pulse / frequency |
| Hazardous area | Hazardous-area rated / option |
Datasheet
Technical features
| Bidirectional measurement, practically independent of pressure, density, temperature and viscosity | |
| No moving parts and no pressure loss from cross-section constriction | |
| Compact dual-compartment transmitter with up to three freely configurable I/Os | |
| Backlit touch-control display with WLAN access; remote display option | |
| Heartbeat Technology for integrated verification | |
| Wide choice of liner and electrode materials for corrosive liquids |
Applications
| Chemical and process plants with corrosive liquids | |
| Hot process liquids up to 180 °C | |
| Pulp & paper chemicals, water and effluent |
Electrical & communication
| Power supply | 24 V DC ±20% or 100–240 V AC (−15…+10%), 50/60 Hz |
|---|---|
| Outputs/inputs | Up to 3: 4–20 mA HART (Ex i option), pulse/frequency/switch, current/status input |
| Fieldbus options | PROFIBUS DP, PROFIBUS PA, Modbus RS485, EtherNet/IP, PROFINET |
| Display | 4-line backlit graphic display, touch control, WLAN |
Key specifications
| Line size | DN 15–600 (½–24 in) |
|---|---|
| Accuracy | ±0.5% o.r. ± 1 mm/s (optional ±0.2% o.r. ± 2 mm/s) |
| Medium temperature | PTFE −40 to 130 °C; PFA −20 to 150 °C; PFA high-temp to 180 °C |
| Liner / electrodes | PTFE or PFA; 1.4435 (316L), Alloy C22, platinum, tantalum or titanium |
| Outputs | Up to 3 I/Os: 4–20 mA HART, pulse/frequency/switch; PROFIBUS DP/PA, Modbus RS485, EtherNet/IP, PROFINET |
| Power / protection | 24 V DC or 100–240 V AC; IP66/67 Type 4X; all common Ex approvals |
Performance
| Measuring range | Typically 0.01 to 10 m/s flow velocity |
|---|---|
| Maximum measured error | ±0.5% o.r. ± 1 mm/s; optional ±0.2% o.r. ± 2 mm/s |
| Repeatability | Max. ±0.1% o.r. ± 0.5 mm/s |
| Minimum conductivity | ≥ 5 µS/cm for liquids in general |
Process
| Nominal diameter | DN 15 to 600 (½ to 24 in) |
|---|---|
| Medium temperature, PTFE | −40 to +130 °C (DN 15–600) |
| Medium temperature, PFA | −20 to +150 °C (DN 25–200) |
| Medium temperature, PFA high-temperature | −20 to +180 °C (DN 25–200) |
| Liner | PTFE or PFA (PFA surface ≤ 0.4 µm) |
| Electrodes | 1.4435 (F316L), Alloy C22, platinum, tantalum, titanium |
| Process connections | EN 1092-1, ASME B16.5, JIS B2220, AS 2129 Table E, AS 4087 PN 16 flanges |
Housing & approvals
| Degree of protection | IP66/67, Type 4X |
|---|---|
| Ambient temperature, transmitter | −40 to +60 °C |
| Hazardous areas | All common Ex approvals |
| Housing | DN 15–300 coated aluminium; DN 350–600 painted carbon steel |
Notes
| Data from the manufacturer's published datasheet. Confirm model, range, materials and approvals with Argonmark before ordering. |
Description
The Endress+Hauser Proline Promag P 300 is an electromagnetic flow meter for chemical and process applications with corrosive liquids and high temperatures, in line sizes from DN 15 to DN 600. With a PTFE or PFA liner and electrodes in 316L, Alloy C22, platinum, tantalum or titanium, it handles liquids from −40 °C up to 180 °C (PFA high-temperature version).
Accuracy is ±0.5% of reading (±0.2% optional) with no moving parts and no pressure loss. The compact transmitter has up to three configurable I/Os, including 4–20 mA HART, pulse outputs and PROFIBUS, Modbus, EtherNet/IP or PROFINET, plus a touch display with WLAN and Heartbeat verification. It runs on 24 V DC or 100–240 V AC and carries all common Ex approvals.
Argonmark Ltd supplies Endress+Hauser instruments across Bangladesh — to pulp and paper mills, water and effluent treatment plants, chemical, textile, food and power plants in Dhaka, Chattogram, Gazipur, Narayanganj and beyond. Send us the model, measuring range, process connection, wetted materials and output you need, and we will confirm the right configuration, lead time and price.
Questions & answers
Customer questions
No questions asked yet. Ask about specification, compatibility, lead time or anything else about this item.
Reviews
No reviews yet. Bought or used this item? Be the first to share your experience.